ACR PowerWatch Voltage Disturbance Recorder
PowerWatch 220/240V is the easiest way to monitor and record essential voltage disturbance information from any 220/240 volt Australian power receptacle. Just set up your pre-determined disturbance threshold values or use the industry standard default values and plug it in. Wire-free for easy and safe power quality monitoring.
- Memory Size: 32 KB (4,000 events)
- Operating Limits: -40°C to 70°C and 0 to 95% RH (non-condensing)
- Certifications: CSA: NRTL/C; UL3111-1
- Clock Accuracy: ± 2 seconds/day
- Dimensions: 85mm x 68mm x 35mm
Suitable for auditing medical instrumentation, point-of-sale terminals, computer servers, and other sensitive electronic equipment.
Please contact us if you have any questions about software compatibility or installation requirements.




Previous
Next
Specifications
Surge, Sag and Outage
Hot to Neutral | Neutral to Ground | |
Range: | 0 to 400V rms | 3 to 200V rms |
Accuracy: | ± 2V rms + resolution | ± 1V rms + resolution |
Resolution: | 2V rms | 1V rms |
Impulse
Hot to Neutral | Neutral to Ground | |
Range: | 100 to 2500V peak | 50 to 2500V peak |
Accuracy: | ± 10% of reading + resolution | ± 10% of reading + resolution |
Resolution: | 10V | 10V |
Width Detection: | 1 μsec minimum | 1 μsec minimum |
Accuracy (phase angle): | ±1° (20 to 180°, 200 to 360°) | ±1° (20 to 180°, 200 to 360°) |
Resolution (phase angle): | 1° | 1° |
Frequency
Hot to Neutral | Neutral to Ground | |
Range: | 45 to 65 Hz | |
Accuracy: | ± 0.1 Hz (3 cycles minimum) | |
Resolution: | 0.1 Hz |
Time
Hot to Neutral | Neutral to Ground | |
Accuracy (events < 1 second): | ± 0.5 cycle | ± 1 cycle |
Resolution (events < 1 second): | 0.5 cycle | 1 cycle |
Accuracy (events > 1 second): | ± 0.2 seconds/day + resolution | |
Resolution (events > 1 second): | 8 seconds |